Customization: | Available |
---|---|
Type: | Combiner Box |
Structure: | Protection |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | DM-CB5 |
Basic | |
Max.PV Array Voltage | 1000V |
Max. PV Array parallel Inputs | 5 |
Rated fuse current(replaceable) | 15A |
Allowable input current | 10A |
Output Circuit Breaker | 60A |
Max. Output current | 50A |
Diameter of wire of input PV array | 2.5 mm² |
Diameter of wire of output PV array | 12 mm² |
Diameter of wire for ground | 10 mm² |
PV dedicated SPD | Yes |
Anti-reverse | Yes |
IP | IP65 |
Size(mm) | 560*500*195mm |
Weight | 16KG |
Environment | |
Normal working temperature/humidity | -25ºC-70ºC,humidity 95% No Condensation,No corrosive gas |
Altitude(m) | <2000m |
Alarm | DC Arc fault state, voltage alarm, current alarm, temperature alarm etc |
Optional | |
Communication Interface | RS485/Modbus-RTU Protocol |
Current monitor for each string | Yes |
Signal Arrester | Yes |
Model | DM-CB08 |
Basic | |
Max.PV Array Voltage | 1000V |
Max. PV Array parallel Inputs | 8 |
Rated fuse current(replaceable) | 15A |
Allowable input current | 10A |
Output Circuit Breaker | 100A |
Max. Output current | 80A |
Diameter of wire of input PV array | 2.5 mm² |
Diameter of wire of output PV array | 16 mm² |
Diameter of wire for ground | 10 mm² |
PV dedicated SPD | Yes |
Anti-reverse | Yes |
IP | IP65 |
Size(mm) | 560*500*195mm |
Weight | 18KG |
Environment | |
Normal working temperature/humidity | -40ºC-70ºC,humidity 95% No Condensation,No corrosive gas |
Altitude(m) | <2000m |
Alarm | DC Arc fault state, voltage alarm, current alarm, temperature alarm etc |
Optional | |
Communication Interface | RS485/Modbus-RTU Protocol |
Current monitor for each string | Yes |
Signal Arrester | Yes |
Model | DM-CB12 |
Basic | |
Max.PV Array Voltage | 1000V |
Max. PV Array parallel Inputs | 12 |
Rated fuse current(replaceable) | 15A |
Allowable input current | 10A |
Output Circuit Breaker | 150A |
Max. Output current | 120A |
Diameter of wire of input PV array | 2.5 mm² |
Diameter of wire of output PV array | 24 mm² |
Diameter of wire for ground | 10 mm² |
PV dedicated SPD | Yes |
Anti-reverse | Yes |
IP | IP65 |
Size(mm) | 670*620*240mm |
Weight | 18KG |
Environment | |
Normal working temperature/humidity | -40ºC-70ºC,humidity 95% No Condensation,No corrosive gas |
Altitude(m) | <2000m |
Alarm | DC Arc fault state, voltage alarm, current alarm, temperature alarm etc |
Optional | |
Communication Interface | RS485/Modbus-RTU Protocol |
Current monitor for each string | Yes |
Signal Arrester | Yes |