Customization: | Available |
---|---|
Application: | Three Phase Transducer |
Output Type: | Triple |
Still deciding? Get samples of US$ 6000/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product Description:
The main function of this series of variable frequency power supply is to convert the municipal power to the required voltage and frequency through power conversion circuit. Its main characteristics are to provide pure and reliable sinusoidal power output, low harmonic distortion, high stability frequency and voltage stabilization rate. It can simulate the output characteristics of different voltages and frequencies in different parts of the world, covering the needs of the whole industry. It fully meets the needs of engineers in design and development, product line testing and product quality assurance, life, over-high/over-low voltage simulation testing, imported equipment and production line power supply applications. In addition, it can support 400 Hz aerospace.
•Inverter core adopts Mitsubishi Inverter Module
•Drive protection using Mitsubishi motor core
•Dynamic reaction rate < 2ms
•Three-phase power supply can adapt to 100% unbalanced load
•Touch screen display, sensitive operation, accurate 0.5 level, good controllability
•It can withstand 2 times rated current (Optional) without voltage drop.
•Frequency stability is less than 1%, load stability is less than 1%, and output frequency is adjustable.
•The output voltage can be adjusted in a wide range. The low-grade voltage can be continuously adjusted from 0 to 150 V, and the high-grade voltage can be continuously adjusted from 0 to 300 V. Low current is twice as high as high current.(Optional)
•Protection level above IP55.
•The output terminal is isolated by transformer, and the harmonic component is small.
•Protection is comprehensive and fast, millisecond response rate, faster and safer step.
Technical Parameters of Three Phase Variable frequency power supply
Type |
LW33-50K |
capacity
|
three phase 50KW |
Circuit way |
IGBT/PWM Delta Modulation Technique
|
Ac Input |
|
input mode
|
three phase four wire |
voltage range
|
380V±25%(Or AC220V AC480V) |
frequency domain
|
50Hz |
Ac Output |
|
Rated capacity |
50KW |
output mode
|
three phase four wire |
Output wave |
Pure sine wave |
output voltage |
AC480±25%(Or AC220V AC380V) |
voltage accuracy
|
±1% |
output frequency
|
60Hz |
frequency accuracy
|
±0.1% |
Output rated current |
60A |
Overload capacity |
110%,3 minutes, 200%,10 second |
Dynamic voltage transient range |
2%(0~100% load change) |
THDV |
THD<3%(nonlinear load) |
Display usage
|
|
Display Window |
Touch screen display |
voltmeters |
precision 0.1V |
current meters |
precision 0.1A |
frequency table |
precision 0.1Hz |
power |
precision 0.1W |
communication |
RS485/RS232/WIFI/GPRS/Enternet(Optional) |
system |
|
system efficiency |
normal mode: 90% |
insulation resistance |
DC> 500V 20MΩ |
dielectric strength
|
(Input and output to the ground)1800Vdc,Leakage current is less than 3.5mA,1 minute without arc |
level of protection
|
IP22 |
mode of connection
|
Output Terminal block |
heat-dissipating method
|
Forced fan refrigeration |
operating temperature |
-10ºC~+50ºC |
relative humidity |
0-90%(without condensation) |
noise(dB) |
<65Db |
Size (mm) |
630×1000×1430mm |
Weight (kg) |
327KG |
Three phase in and three phase out 150K
Power type |
Three phase in and three phase out |
|
Capacity |
150KVA |
|
Circuit mode |
IGBT/SPWM |
|
AC Input |
Phase number |
Three-phase four-wire + ground wire |
Input voltage range(Vac) |
480V±15% |
|
Input frequency range(Hz) |
30-70 |
|
AC output |
Phase number |
Three-phase four-wire + ground wire |
Wave form |
Pure sine wave |
|
Output Voltage(V) |
380Vac |
|
Output Voltage Accuracy(V) |
≤1% |
|
Output frequency range(Hz) |
45-65 |
|
Output Frequency Accuracy(Hz) |
≤0.01% |
|
Output rated current(A) |
197A/180A/126A | |
THD |
≤3% |
|
Dynamic response time |
2ms |
|
Power factor(PF) |
0.8 |
|
Overload capacity |
110%,10min;200%,10s |
|
Peak Coefficient(CF) |
3:1 |
|
Efficiency |
≥90%(Resistive load 80%) |
|
Display |
Type |
LED/Touch Screen |
Communication |
RS485/RS232/WIFI/GPRS |
|
Environment |
Insulation strength |
1500VAC,1min |
Noise (1 m) |
≤55dB |
|
Ambient temperature |
-10ºC~+50ºC |
|
Humidity |
0-90%(No condensation) |
|
Altitude(m) |
≤2000m |
|
Indicator light |
Electricity, Inverter (Power Supply, Overvoltage, Undervoltage, Overcurrent, Overheat, LED Model Configuration) |
|
Protection |
Input connection, input under voltage, output over voltage , output over current , output overload , output short circuit , overheat |
|
Cooling mode |
Fan |