| Customization: | Available |
|---|---|
| After-sales Service: | Yes |
| Warranty: | 1-5 Years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency

| AC Side parameters | |||
| Operation mode | Continuous | ||
| AC wiring mode | Three phase four wire | ||
| Rated output power | 50KW | 100KW | 200KW |
| Output overload capacity | 55KW | 110KW | 220KW |
| DC Side Parameters | |||
| Maximum DC power | 55KW | 110KW | 220KW |
| DC voltage range Vdc | 350-800Vdc | 350-800Vdc | 350-700Vdc |
| Recommended battery bank voltage | 384V/420V/480V | 420V/480V | 480V |
| Rated charge current | 130A/119A/104A | 238A/208A | 416A |
| Max. Input current | 143A/130A/115A | 262A/229A | 458A |
| Voltage stabilization accuracy | ±1% | ±1% | ±1% |
| Steady current accuracy | ±1% | ±1% | ±1% |
| DC current ripple | <1% IPP | <1% IPP | <1% IPP |
| On Grid charging and discharging mode Constant power | |||
| Rated grid voltage(AC) | 220V / 380V / 440V | 220V / 380V / 440V | 220V / 380V / 440V |
| Grid voltage range(AC) | ±20% | ±20% | ±20% |
| Rated grid frequency | 50Hz / 60Hz | 50Hz / 60Hz | 50Hz / 60Hz |
| Grid frequency range | ±10% | ±10% | ±10% |
| Rated power(THD) | <3%(Standard grid) | ||
| Power factor | -0.8~+0.8 | ||
| Independent inverter mode | |||
| Rated output voltage(AC) | 220V / 380V / 440V±1% | ||
| Output voltage distortion | <3% ( resistive load) | ||
| Rated output frequency | 50Hz / 60Hz±1% | ||
| Voltage transition range | <10% (Resistance load 0% <=>100%) | ||
| System Parameters | |||
| On/off-grid switching time | 0ms | ||
| Max. conversion efficiency | 95%( Include isolation transformer) | ||
| Noise | <60dB | ||
| Protection Degree | IP20 | ||
| Working Temperature | -25ºC~+45ºC | ||
| Cooling method | Air cooling | ||
| Working humidity | 0~95% | ||
| Working altitude | ≤6000m, 2000m(Reduced usage for more than 2000m) | ||
| Emergency stop | Yes (via emergency stop button) | ||
| Display | Touch screen | ||
| Communication mode | RS485,WIFI,GPRS,Ethernet (Modbus protocol) | ||
| Dimensions | 750*600*1320mm | 1460*860*1820mm | 1460*860*1820mm |
| Weight | 340KG | 1.4t | 1.6t |


Deming Power energy storage products and system solutions solve power supply problems in areas with no and weak electricity, and achieve smart power supply and demand allocation. This system is designed for three-phase energy storage system, which can realize the functions of On grid power generation, off-grid inversion, and city power reverse charging. If the power grid is disconnected, the storage system can automatically and seamlessly switch to off-grid operation mode to ensure uninterrupted power supply.
The PCS in this system, is built-in MPPT solar charging module, integrated EMS management system. It can realize that the solar panels provide power to the load preferentially through PCS, and the excess electricity is used to charge the battery. When the battery is fully charged, the electricity from the solar panels is fed into the grid through PCS.