Model | NB48-5KDZ | NB96-5KDZ | NB120-5KDZ | NB240-5KDZ | |
DC input | Input rated voltage | 48 VDC | 96 VDC | 120 VDC | 23 VDC |
Input rated current | 116A | 58A | 46A | 22.7A | |
Input DC voltage allowing range | 40-62VDC | 80-124 VDC | 100-155 VDC | 200-310 VDC | |
AC bypass | Allow input voltage range | 110 VAC / 120 VAC / 220 VAC / 240 VAC ± 15% | |||
Input rated current | 45.5A / 41.7A / 22.5 A / 21A | ||||
Bypass transfer time | ≤40 ms(Can be customized ≤4ms version) | ||||
AC output | Output rated power | 5KW | |||
Output rated voltage and frequency | 110 VAC / 120 VAC / 220 VAC / 240 VAC,50Hz / 60Hz | ||||
Output rated current | 45.5A / 41.7A / 22.5 A / 21A | ||||
Output voltage accuracy | 110 VAC / 120 VAC / 220 VAC / 240 VAC± 1% | ||||
Output frequency accuracy | 50Hz / 60Hz ± 0.05% | ||||
Wave | Pure sine wave (Isolation transformer) | ||||
THD. | ≤3%( Linear load) | ||||
Power factor (PF) | 1 | ||||
Overload capacity | 120%,5 minutes;200%,3 seconds | ||||
Crest factor (CF) | 3:1 | ||||
Inverter efficiency | >94% | ||||
Working Environment | Dielectric strength | 1500VAC,1 minute | |||
Noise (1m) | ≤50dB | ||||
Ambient temperature | -20ºC~+60ºC | ||||
Humidity | 0~90%, No condensation | ||||
Altitude | <6000m(Higher than 2000m rated power should be reduced) | ||||
Equipped with Isolated Transformer | Yes | ||||
Battery priority | Yes | ||||
Communication Interface | RS485 | ||||
Production function | Input reverse protection, input under-voltage protection, output overload protection, output short circuit protection, thermal protection | ||||
Size | 510*660*850 mm | ||||
Weight | 58 Kg |
Type | NB48-7.5KDZ | NB96-7.5KDZ | NB120-7.5KDZ | NB240-7.5KDZ | |
DC input | Input rated voltage | 48 VDC | 96 VDC | 120 VDC | 240 VDC |
Input rated current | 174A | 87A | 69A | 35A | |
Input DC voltage range | 40-62 VDC | 80-124 VDC | 100-155 VDC | 200-310 VDC | |
AC input | Allow input voltage range | 110 VAC / 120 VAC / 220 VAC / 240 VAC ± 15% | |||
Input rated current | 68A / 62.5A / 34A /31A | ||||
Bypass transfer time | ≤40 ms(Can be customized ≤4ms version) | ||||
AC output | Output rated power | 7.5KW | |||
Output rated voltage and frequency | 110 VAC / 120 VAC / 220 VAC / 240 VAC,50Hz / 60Hz | ||||
Output rated current | 68A / 62.5A / 34A / 31A | ||||
Output voltage accuracy | 110 VAC / 120 VAC / 220 VAC / 240 VAC± 1% | ||||
Output frequency accuracy | 50Hz / 60Hz ± 0.05% | ||||
Waveform distortion (THD). | ≤3% (Linear load) | ||||
Dynamic response time (Load 0←→100%) |
2ms | ||||
Power factor (PF) | 1 | ||||
Overload capacity | 120%,5 minutes;200%,3 seconds | ||||
Crest factor (CF) | 3:1 | ||||
Inverter efficiency | 94% | ||||
Working Environment | Dielectric strength | 1500VAC,1minute | |||
Noise (1m) | ≤50dB | ||||
Ambient temperature | -20ºC~+60ºC | ||||
Humidity | 0~90%, No condensation | ||||
Altitude | <6000m(Higher than 2000m rated power should be reduced) | ||||
Production function | Input reverse protection, input under-voltage protection, output overload protection, output short circuit protection, thermal protection | ||||
Equipped with isolated transformer | Yes | ||||
Pure Sine Wave | Yes | ||||
AC Charger | Available, optional | ||||
Solar Battery Charger | Available, optional | ||||
Dry Contact | Available. optional | ||||
Size | Net Size: 400*660*770mm Packing Size:500*780*930 | ||||
Weight | Net Weight :105KGS Gross Weight :126KGS |