Still deciding? Get samples of $ !
Request Sample
|
| Customization: | Available |
|---|---|
| Nature of Source Flow: | Passive inverter |
| Output Power: | >1000W |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Power Frequency Pure Sine Wave Inverter Features:
1.Complete isolation-type inverter technology, noiseless output.




20KVA off grid single phase inverter technical parameters
| Model | NB96-20KDZ | NB110-20KDZ | NB220-20KDZ | |
| DC input | Input rated voltage | 96 VDC | 110 VDC | 220 VDC |
| Input rated current | 231.5 A | 202 A | 101 A | |
| Input DC voltage allowing range | 80-124 VDC | 90-140 VDC | 180-280 VDC | |
| AC input (AC bypass) |
Allow input voltage range | 110 VAC / 120 VAC / 220 VAC / 240 VAC ± 15% | ||
| Input rated current | 182A / 167A / 91 A / 83A | |||
| Bypass transfer time | ≤40 ms (4ms optional) | |||
| AC output | Output rated power | 20KVA | ||
| Output rated voltage and frequency | 110 VAC / 120 VAC / 220 VAC / 240 VAC,50Hz / 60Hz | |||
| Output rated current | 182A / 167A / 91 A / 83A | |||
| Output voltage accuracy | 110 VAC / 120 VAC / 220 VAC / 240 VAC± 2% | |||
| Output frequency accuracy | 50Hz / 60Hz ± 0.05% | |||
| Wave | Pure sine wave (Isolation transformer) | |||
| THD. | ≤3%(Linear load) | |||
| Power factor (PF) | 0.8 | |||
| Overload capacity | 120%,10 minutes | |||
| Overcurrent capacity | 200%,10 seconds | |||
| Crest factor (CF) | 3:1 | |||
| Inverter efficiency | >90% | |||
| Working Environment | Dielectric strength | 1500VAC,1minute | ||
| Noise (1m) | ≤50dB | |||
| Ambient temperature | -10ºC~+50ºC | |||
| Humidity | 0~90%, No condensation | |||
| Altitude | <2000m Higher than 2000m rated power should be reduced |
|||
| Production function | Input reverse protection, input under-voltage protection, output overload protection, output short circuit protection, thermal protection | |||
| Communication interface | RS485/WIFI/GPRS/Ethernet (optional) | |||
| Equipped With Copper Transformer | Yes | |||
| Solar Charger | Optional | |||
| AC Charger | Optional | |||
| Generator Port | Optional | |||
| Size | 620*1040*1100 mm | |||
| Weight | 220 Kg | |||
*Above parameter only for reference. Could be custom made to user specifications.